“never plug extension cords into extension cords” is probably the most common piece of electrical related advice I’ve ever heard. But if you have, say, 2 x 2m long extension cords, and you plug one into the other, why is that considered a lot more unsafe than just using a single 4 or 5 meter cord?

Does it just boil down to that extra connection creating another opportunity for the prongs to slip out and cause a spark or short circuit? Or is there something else happening there?

For that matter - why aren’t super long extension cords (50 or more meters) considered unsafe? Does that also just come down to a matter of only having 2 connections versus 4 or more on a daisy chained cord?

Followup stupid question: is whatever causes piggybacked extension cords to be considered unsafe actually that dangerous, or is it the sort of thing that gets parroted around and misconstrued/blown out of proportion? On a scale from “smoking 20 packs of cigarettes a day” to “stubbing your toe on a really heavy piece of furniture”, how dangerous would you subjectively rate daisy chaining extension cords, assuming it was only 1 hop (2 extension cords, no more), and was kept under 5 or 10 metres?

I’m sure there’s probably somebody bashing their head against a wall at these questions, but I’m not trying to be ignorant, I’m just curious. Thank you for tolerating my stupid questions

  • douglasg14b@lemmy.world
    link
    fedilink
    arrow-up
    1
    ·
    16 minutes ago

    Connectors come loose, which makes them dangerous.

    They are uninsulated points that allow water and material ingress, and can partially or fully pull apart, causing arching. Which can cause combustion.

    This is the main reason these are dangerous, which the majority of this entire thread misses. The added length or connector resistance is somewhat negligible here unless you’re daisy chaining long conductors, which often isn’t the case for in-home extensions.

  • uis@lemm.ee
    link
    fedilink
    arrow-up
    8
    arrow-down
    1
    ·
    edit-2
    34 minutes ago

    On a scale from “smoking 20 packs of cigarettes a day” to “stubbing your toe on a really heavy piece of furniture”, how dangerous would you subjectively rate daisy chaining extension cords

    As dangerous as one extension cord of their combined length. Don’t forget to verify that every cord rating is above load rating. I recommend to use at least same rating as circuit breaker or get extension cord with circuit breaker built in and never decrease rating down the line without circuit breaker before it, so even if you somehow overload it, there will be protection from it.

    AND NEVER COIL OR THERMALY INSULATE! Cords rely on convection for heat dissipation, and spooling and insulating reduces it, thus increasing electrical insulator temperature until it melts and spontaneously combusts. This applies to extension cords in general.

    • tacosplease@lemmy.world
      link
      fedilink
      arrow-up
      8
      ·
      6 hours ago

      Because this is the Internet, I’ll be pedantic and say the interface where each cord plugs into the next probably adds some resistance as well.

      So, 50 cords 1 ft each plugged into each other would have a higher resistance than the same wire at a single 50ft length.

      I doubt it really matters in the practical terms of your answer and the question being asked though.

  • JordanZ@lemmy.world
    link
    fedilink
    arrow-up
    32
    arrow-down
    3
    ·
    edit-2
    15 hours ago

    Others have pretty much mentioned it. Too thin of conductors for the total length required which can overload the cable and heat it up. If you’re just charging your phone it’s unlikely to cause a problem but the more amps you pull the riskier it gets.

    Here’s a helpful chart…

    Edit: Even at harbor freight (cheap hardware store) a 50ft 12 gauge extension cord is about $40 and weighs 7 pounds.

  • Free_Opinions@feddit.uk
    link
    fedilink
    arrow-up
    20
    ·
    edit-2
    16 hours ago

    Related thing about extension cable reels that many don’t know is that even if you need like 3 meters of cable you should still unspool the entire thing as otherwise it’s acting as a coil and creating resistance heat. Most cable reels have different ratings marked on them for when they are spooled / unspooled. This is especially true when the device you’re powering takes >1000 watts

    • modeler@lemmy.world
      link
      fedilink
      arrow-up
      14
      arrow-down
      2
      ·
      16 hours ago

      Many years ago, my mother used the electric lawn mower without unspooling all the wire. When it finally shorted, all the plastic wire insulation was in the process of turning into a melty plastic soup. A Lesson Was Learned.

      The reason isn’t resistance - it’s that the coiled wire makes an electromagnet that stores energy in the magnetic field. The alternating current in the mains switches 50 or 60 times a second. In each cycle the magnetic field is created, destroyed then recreated in the opposite direction, then destroyed. This dumps a lot of energy (and therefore heat) into the coil.

      • brown567@sh.itjust.works
        link
        fedilink
        arrow-up
        4
        ·
        11 hours ago

        The coil wouldn’t make a significant magnetic field because the cable has two wires with opposite current flow in close proximity

        But when the cable is coiled, its ability to dissipate heat is less, so normal resistive heating can create higher temperatures

    • Baku@aussie.zoneOP
      link
      fedilink
      English
      arrow-up
      17
      arrow-down
      1
      ·
      1 day ago

      Thanks for the response! Would you mind going a bit more in depth about that please? I could understand increasing the risk of overload if you were to daisychain power boards, as they add more power points to the circuit than it was designed for. But extension cords (at least in my experience) only have 2 ends - one with a single plug receptacle, and the other that plugs into a power point

      Is it the actual connection between the two that adds more resistance to it? If it were the wiring, then wouldn’t that also pose a problem for longer extension cords?

      In either case, what sort of resistance add are we talking about (feel free to pick random lengths of examples make it easier to explain)?

      • Nougat@fedia.io
        link
        fedilink
        arrow-up
        102
        arrow-down
        8
        ·
        1 day ago

        The longer the cable, the thicker (heavier gauge) it needs to be to carry the same current without burning up. One extension cord is rated to carry the current it alone is able to carry. Put two of those in series, and both of them together are able to carry less current than either one by itself. This is how fires start.

        • gaiussabinus@lemmy.world
          link
          fedilink
          arrow-up
          30
          arrow-down
          8
          ·
          22 hours ago

          This is incorrect. I need to increase gauge for voltage drop. Overloading the cable via length can only happen if I have a motor or other magnetic load at the end. A motor will try to draw it’s designed wattage regardless of voltage. A wire of a given ampacity will handle that many amps regardless of the length of the conductor. The relationship is power = voltage x current and voltage = current x resistance for single phase. The fire concern on extension cords tied together indoors is you have 100% strung that shit through a doorway or window, which is a code violation. You are going to pinch it and burn your shit down. all outdoor plugs are gfci these days and on site i can have 4 or 5 extension cords tied together. i only get 109 volts at the end but a heater is a resistive load. Doesnt matter for that application.

          • fine_sandy_bottom@lemmy.federate.cc
            link
            fedilink
            arrow-up
            18
            arrow-down
            2
            ·
            20 hours ago

            It’s obvious you know more or less all there is to know about this topic. So much so that I suspect you have trouble explaining it to laypersons like me because it’s difficult for you to determine which parts of your knowledge are obvious common knowledge and which parts are specialist knowledge.

            • gazter@aussie.zone
              link
              fedilink
              arrow-up
              7
              ·
              11 hours ago

              The super simple explanation is that the wires are too small. The water hose analogy breaks down fairly quickly, but I’ll try using it. Imagine a garden hose, with a regular nozzle on the end. But it’s not a perfect world, and our hose doesn’t transfer all the water that goes into it. Think of this as ten pinprick holes along every meter of hose. If we have ten meters of hose, that’s fine, we only need to turn on the tap a little bit to get a decent spray out of the nozzle, and a little bit will dribble out these holes. Now let’s join another hose on. We lose more water to leakage, so to get the same amount of water out of our nozzle, we have to turn on the tap more, giving it a bit more water flow. Now, our pinprick holes are not just dribbling, they’re flowing freely. Now let’s take it to the extreme- we join a thousand garden hoses together, all leaking a little bit. We have to turn the tap on A Lot More, and suddenly our pinpricks are spraying a serious amount of water everywhere. Now imagine we use a bigger hose. Let’s take it to the extreme again and say it’s a big stormwater pipe. But the key part here is that it has the same amount of holes, ten pinpricks per meter. This way, we can get heaps more water down that pipe, more than enough to give that water nozzle everything it wants. Also, because our pressure can remain low, those pinpricks are only leaking a little bit, not spraying everywhere. This is getting pretty wordy and unwieldy to type out on my phone, so I’ll try and bring it into the real world a bit more. An electrical load, like a motor (say a compressor in a fridge, a circular saw, etc) is like to our nozzle. It will pull more current (amps, or water flow) to maintain the same amount of power output (water coming out of the nozzle). As we get a longer conductor, the voltage drop (pressure reduction due to water lost to the pinpricks) gets larger, and our voltage at the end of a conductor gets lower. Power = voltage * current, so if that voltage is lower, to get the same power we need more current. More current means more heating. More heat in a small cable means melting. Physics has a way out for us, thankfully! The thicker a cable is, the less voltage drop it has, kind of like our stormwater pipe. So the voltage remains at a normal level at the motor, and consequently the motor draws a normal amount of current. This is why longer extensions are generally a lot thicker than shorter ones. If you’re interested in the math, let me know, it’s actually pretty fascinating, and ties into why long distance power lines are all super high voltage, among many other things. The basic equations are also not too hard to work with.

                • lightnsfw@reddthat.com
                  link
                  fedilink
                  arrow-up
                  1
                  ·
                  edit-2
                  8 hours ago

                  My high school had a lot of vocational courses. I took auto shop, construction, welding, and small engine mechanics. Several of those covered electricity.

          • AgentOrangesicle@lemmy.world
            link
            fedilink
            arrow-up
            1
            ·
            edit-2
            19 hours ago

            Do you mean inductive load rather than magnetic load? Or are all inductive loads attributed to electromagnets?

            Edit: also, don’t like… a lot of appliances create inductive loads?

            • gaiussabinus@lemmy.world
              link
              fedilink
              arrow-up
              4
              ·
              14 hours ago

              Most inductive loads are motors. I used the term magnetic rather than inductive in the Hope of making my response less jargon filled and more intelligible. Very generally speaking inductance is the magnetic portion of the circuit or more technically it would the contribution to the circuit that causes the wave form to lag. That is specific to an AC circuit.

          • Nougat@fedia.io
            link
            fedilink
            arrow-up
            13
            arrow-down
            2
            ·
            1 day ago

            Another bit of explanation I just thought of –

            Think of an incandescent light bulb. It has a filament. You run electricity through the filament and it heats up enough to glow, producing light to see by. It does that because the thin filament has high resistance; it resists allowing current to flow through it.

            Any piece of conductive material will do the same thing if you put enough current through it. Even an extension cord. It will heat up enough to glow. Being an extension cord, it will then melt the insulation and dramatically increase the likelihood of setting something on fire.

            • ch00f@lemmy.world
              link
              fedilink
              arrow-up
              6
              ·
              edit-2
              23 hours ago

              This is primarily a concern because extension cords aren’t fused, and there’s no control over how they are routed.

              Most wiring in your walls come after a circuit breaker and are designed to allow for a certain amount of heating. The electrician follows a code that guarantees that the circuit breaker will trip before there’s any possibility of too much heat. This table indicates a higher ampacity rating for higher temperature ratings.

              Now most extension cords are made cheaper by using lower gauge than the wiring in your walls. The general assumption is that they’re spread out, so the heat has no way to build up, and you won’t be plugging them permanently into something drawing the peak 15A allowed by the circuit breaker.

              If you were to pile up a 100 foot extension cable and plug in a hairdryer, you’d probably start a fire. If it was all spread out, likely your hair dryer would just receive less than the 120V it’s expecting, and it wouldn’t get very hot.

              Ironically, dinky christmas lights make very safe extension cords because they’re fused inside the plug.

            • SzethFriendOfNimi@lemmy.world
              link
              fedilink
              arrow-up
              6
              arrow-down
              1
              ·
              23 hours ago

              And because the wire gauge is less than the wiring in the wall the breaker won’t trip before it reaches the point where it’s overloaded either.

            • Aqarius@lemmy.world
              link
              fedilink
              arrow-up
              1
              ·
              18 hours ago

              It does that because the thin filament has high resistance;

              Other way around. Low resistance - high power.

        • flambonkscious@sh.itjust.works
          link
          fedilink
          English
          arrow-up
          2
          ·
          1 day ago

          I wonder what kind of safety margin is calculated into these…

          Admittedly I’ve seen some wildly different shielding or thickness in my time

          • Nougat@fedia.io
            link
            fedilink
            arrow-up
            10
            arrow-down
            1
            ·
            24 hours ago

            For extension cords? Pretty much nothing. They can be dangerous all by themselves. You have an outlet on a 15A circuit. You can plug all sorts of things into that outlet all at the same time, especially if you’re daisy chaining cords and adapters. The sum total of current from all those things can be less than 15A, so the circuit breaker never trips, but more than what your mess of extension cords can handle. Even worse, if it’s just a little more than the extension cords can handle, you might not notice right away, and then you’ll come home later to a pile of smoldering ash.

            Don’t chain extension cords.

      • FourPacketsOfPeanuts@lemmy.world
        link
        fedilink
        arrow-up
        11
        arrow-down
        2
        ·
        1 day ago

        I don’t think what they said is actually a problem, it’s just a back-justification for the original trope. Daisy chaining them and strictly sticking to only the few appliances that would fit in one extension strip is fine. But that’s complicated to explain, it’s better to just tell people not to do it rather than expect them to understand what’s going on

        A couple things that can happen…

        • plugging in too many appliances over several daisy chained power strips trips the circuit breaker because too much current is being drawn

        • if the country you live in has lax electrical safety standards then, yes, perhaps you can overload the daisy chain without tripping the main circuit which would lead to overheating

        • Eheran@lemmy.world
          link
          fedilink
          arrow-up
          6
          ·
          23 hours ago

          When the breaker trips then the fundamental issue is unlikely to be present. But to be able to push enough current to cause it to break the connection needs to have a sufficiently low resistance. If that gets too high it will never break, even if you short the cables. And that will result in a fire, because the protection does not work anymore. That is the dangerous part.

    • Zacryon@feddit.org
      link
      fedilink
      arrow-up
      4
      arrow-down
      1
      ·
      22 hours ago

      Isn’t the added cable resistance small enough to not cause issues so soon? In case you just chain a few ( < 10 ) together.

      • Cort@lemmy.world
        link
        fedilink
        arrow-up
        10
        arrow-down
        1
        ·
        edit-2
        22 hours ago

        It’s not just the cable resistance, but the added resistance at each connection point. Since the plugs aren’t the same piece of metal, just touching.

  • BillibusMaximus@sh.itjust.works
    link
    fedilink
    arrow-up
    64
    arrow-down
    3
    ·
    1 day ago

    The longer the distance, the larger the diameter of the wire you need, due to resistance/heat.

    Typically, extension cords are going to be manufactured with the thinnest wire they can get away with based on the safety requirements, in order to save on materials cost.

    So plugging 2 short cords together might cover the same distance as 1 longer cord, but the longer cord will use thicker wire to maintain the proper margin of safety.

    • douglasg14b@lemmy.world
      link
      fedilink
      arrow-up
      1
      ·
      edit-2
      21 minutes ago

      Distance by itself would be no different than a single cord of the same length.

      However, connection points are areas of localized resistance where connectors meet. This can introduce dangerous areas.

      That said, those aren’t really the problem here:

      The practical, human, problem here is important. Connectors come loose, which makes them dangerous. The majority of this thread is treating this question like a paper test problem, when in reality there are other factors that outweigh the “under ideal circumstances” problem.

    • scarabic@lemmy.world
      link
      fedilink
      English
      arrow-up
      7
      ·
      edit-2
      18 hours ago

      Said another way: Each cable is given the minimum copper and shielding that cable needs for the length it is made.

      As soon as you plug two together, you’re operating at greater resistance than either one was made for, and relying on the margin of error.

    • uis@lemm.ee
      link
      fedilink
      arrow-up
      1
      arrow-down
      6
      ·
      11 hours ago

      The longer the wire, the more heat it can dissipate, so no, you don’t need wire to be thicker.

      • gazter@aussie.zone
        link
        fedilink
        arrow-up
        3
        ·
        6 hours ago

        Not sure if you’ve ever used fuse wire before. It’s what was used before capsule fuses and breakers. Essentially, if too much current goes through it, it will melt, breaking the circuit as protection. The thicker the fuse wire, the more current it can pass through without melting. The length of the wire doesn’t come into it. 1cm of 10 amp fuse wire will melt at the same current as 1 meter of 10 amp fuse wire.

    • kevincox@lemmy.ml
      link
      fedilink
      arrow-up
      5
      arrow-down
      3
      ·
      21 hours ago

      But unless coiled up on the ground the longer cable also has more area to dissipate heat, so the longer cable doesn’t change anything here. The heat output will be consistent for any section of the cable no matter how much more cable there is on easier side of it.

      The only think that the different resistance would affect is the voltage drop to the end device. But voltage drop varies wildly so you are unlikely to have a meaningful difference caused by a few extension cords (unless maybe you are already a bad case like an apartment building to start).

      • Xtallll@lemmy.blahaj.zone
        link
        fedilink
        English
        arrow-up
        2
        arrow-down
        4
        ·
        18 hours ago

        Resistance of a cable is (resistivity x Length)/(πr^2) so the residence increases with length, which is why longer extension cords are designed thicker to reduce resistance. Power grids are voltage stabilized so the voltage drop will be negligible but it will take more power to get down the daisy chain, producing more heat.

        • uis@lemm.ee
          link
          fedilink
          arrow-up
          1
          arrow-down
          1
          ·
          10 hours ago

          And temperature difference to ambient temperature is thermal resistivity * dissipated power / (2\*π\*radius\*length). If you will plug dissipated power = resistance * current^2 and resistance into it, you will see, that temperature difference is invariant of length.

      • HeckGazer@programming.dev
        link
        fedilink
        arrow-up
        1
        arrow-down
        2
        ·
        19 hours ago

        The longer wire (being also thicker) has less resistance and is therefore wasting less power as heat, that’s where the Voltage drop is going.

        Sure, most of the time it’s fine if you know what you’re doing, but that’s why it’s general wisdom and not a hard rule, like “don’t put metal in the microwave”, it’s said to protect those that have no idea what they’re doing/why the saying exists

    • Baku@aussie.zoneOP
      link
      fedilink
      English
      arrow-up
      17
      ·
      edit-2
      23 hours ago

      This, along with hotels that hide their only power point behind the bed but have 50 bloody phone jacks, are my pet peeves. But it kinda makes sense when you consider they were mostly built before the days of having a ton of devices in the bedroom. A lamp and alarm clock, maybe a TV if you’re well off, would’ve been perfectly fine for a lot of people

      • glimse@lemmy.world
        link
        fedilink
        arrow-up
        13
        ·
        24 hours ago

        The absolute worst is when the Word Documents are stashed away in some random drawer. Or when you find an Excel spreadsheet under the mattress!

        • kungen@feddit.nu
          link
          fedilink
          arrow-up
          9
          ·
          24 hours ago

          Not so awful, but it’s disappointing when you open the drawer expecting a Bible, but there’s only OneNote there.

        • Baku@aussie.zoneOP
          link
          fedilink
          English
          arrow-up
          4
          ·
          23 hours ago

          I really wish my autocorrect would stop doing that. I can count on one hand the amount of times I’ve actually wanted to write “PowerPoint”. I couldn’t even count on 10 hands the amount of times it’s assumed I’m some kind of idiot that doesn’t know “PowerPoint” is a single word when I type “power point”

      • litchralee@sh.itjust.works
        link
        fedilink
        English
        arrow-up
        0
        ·
        23 hours ago

        I once read a theory on an electricians forum about how the USA electrical code’s mandated maximum distance between adjacent outlets on a wall, coupled with the typical bedroom layout, as well as home builders trying to be as cheap as possible, led to only a single outlet being placed directly in the middle of the longest wall. This is also the most logical position for a bed, so the theory is that the bed pressing against the outlet over time was a contributing factor to electrical-related house fires.

        I cannot find where I read that originally, and certainly the granularity of nationally-reported fire data is not sufficient to prove that theory. And while the electrical code’s distance requirements haven’t changed, more homes will now put enough outlets so the only one isn’t behind the bed.

    • Boozilla@sh.itjust.works
      link
      fedilink
      English
      arrow-up
      8
      ·
      23 hours ago

      Years ago, I used to play live music. We played in a lot of shitty dive bars. Thinking back on all the ancient decrepit plugs we used to power our instruments, amplifiers, and stage lights with…it’s a miracle we never started a fire. Nightmare fuel now that I’m older and a little bit wiser.

  • Dark Arc@social.packetloss.gg
    link
    fedilink
    English
    arrow-up
    26
    arrow-down
    1
    ·
    1 day ago

    There are two things going on here.

    The first is that yes, more connections causes more opportunities for the plugs to slip. So you can get short circuits or even arcing that can start a fire.

    The second is that the wire in the cord has a certain rating on it. Many of those cords do not use 12 (20 amp) or 14 (15 amp) gauge wire; so, they’re not rated for the full capacity of the wire in the wall. The breakers are sized to protect the wires in the wall, they don’t know anything about the things plugged into them. So what can happen is you plug too much into the extension cord (particularly if it’s a power strip) and the load on the extension cord is not enough to trip the breaker (because the walls are fine) but it’s enough to overload the extension cord wire. In other words, the extension cord can start getting so hot it melts and possibly arcs up as the insulation fails.

    You can have a fire from overloading a single power strip in just the same way. However, the more you chain together, the more likely you are to overload the power strip.

    Ideally, you just think about what you’re doing… But historically the easy answer is just to tell people not to chain things.

    In short it’s not about the distance, it’s about the insulation and quality of the wire itself along with the number of connections.

    • Baku@aussie.zoneOP
      link
      fedilink
      English
      arrow-up
      4
      ·
      1 day ago

      Awesome answer - thank you!!

      Although I guess a more general question - why aren’t all power boards and extension cords mandatorily fitted with their own circuit breakers/overload protection circuits? I guess it’s cheaper to just tell people never to daisy chain, but at the same time, when you factor in overall costs incurred by anybody (or insurance companies, etc) from people unintentionally overloading them and causing them to melt and burn down houses, wouldn’t it be in everybody’s best interests to raise the price a few dollars and include a resettable overload protection system?

      • Catoblepas@lemmy.blahaj.zone
        link
        fedilink
        arrow-up
        9
        ·
        edit-2
        23 hours ago

        Technology Connections made a 25 minute video about American extension cords and why they’re dangerous, if you want to watch a long form answer.

        Edit: oops, just saw I’m late to the party with this video

      • DaPorkchop_@lemmy.ml
        link
        fedilink
        arrow-up
        7
        ·
        24 hours ago

        iirc British plugs do have a fuse built in to every plug, but they are also the only ones who do that

      • Dark Arc@social.packetloss.gg
        link
        fedilink
        English
        arrow-up
        5
        ·
        24 hours ago

        Some power systems do actually put a fuse in the extension cord… I think it’s the UK that does this. Basically every power system other than the US uses different (safer) plug designs that solve the arcing problem.

        In practice daisy chaining rarely causes a serious problem and it makes things more expensive so it never really became a thing that was legislated or common within the US. Similar to how the plug designs themselves rarely cause a problem so it hasn’t made sense to actually change them.

  • SolOrion@sh.itjust.works
    link
    fedilink
    arrow-up
    15
    ·
    1 day ago

    First, I’m not an electrician, or anything even vaguely approaching one.

    I’ve never heard that advice with extension cords, only power strips.

    You could theoretically link enough extension cords together to cause problems, but it would need to be some extremely shit extension cords or a LOT of them. Resistance increases over distance, which in power cables manifests as them getting hotter. That isn’t a problem until all the sudden it is a problem.

    For power strips, the main danger is that you’re potentially introducing more outlets than any of them are rated for. If you’re just using 2 3ft power bars to functionally make a 6ft cable that you’re only plugging a single thing into… you’re fine. Or at least I was, idk I did it for like a whole year. If you’re plugging 16 things into a single wall outlet via power strips you can trip the circuit breaker, or potentially much worse stuff can happen like things getting melty and starting a fire.

    If you know enough of what you’re doing to math out the power draw+what your outlet/power strips are rated for you can pretty (afaik) safely daisy chain them if you wanna.

    • kevincox@lemmy.ml
      link
      fedilink
      arrow-up
      4
      ·
      20 hours ago

      Yeah, there are two components here

      1. Adding extra length.
      2. Adding more outlets.

      2 is the main problem, but you need a little of 1 to have it fail in an unsafe way (ie. not just tripping the circuit breaker).

      If you just add a lot of extra outlets and plug lots of stuff in then you will simply trip the circuit breaker. (Assuming that everything is properly set up according to code.) In order to create a problem you need some extra wiring that is rated for less load than the wall wiring. (Now in practice every splitter has some amount of wiring, so these can be the same device, but most power bars are rated to be “fully used” or have a fuse internally). So the problem looks something like this:

      1. Have a 20A wall circuit.
      2. Plug a 10A extension cord into it.
      3. Plug a power bar or other splitter into the extension cord.
      4. Put enough devices into the splitter to generate 15A of current.

      Now you are overloading the extension cord and risking fire.

  • Boozilla@sh.itjust.works
    link
    fedilink
    English
    arrow-up
    10
    ·
    24 hours ago

    The smart answer: it can start a fire, don’t do it.

    The honest answer: I’ve done it a zillion times and never started a fire. I buy heavy 12 and 10 gauge cords and only chain them to power things that don’t require a lot of amps, like LED lights.

    When in doubt, a plug-in power meter is an option you can use to help monitor the situation. Plugs that draw a lot of amps can get warm, even when not using an extension cord. Also, it’s not uncommon for a device to pull a lot of amps on initial power-up, and then settle down to a lower draw.

  • litchralee@sh.itjust.works
    link
    fedilink
    English
    arrow-up
    8
    ·
    edit-2
    23 hours ago

    I’m not trying to be ignorant, I’m just curious.

    I think you’re in the right community! Don’t let anyone tell you to shy away from asking curious questions. (well, unless the question is also bigoted, illegal, baiting, sealioning, or otherwise disingenuous)

    I’m not an electrician in any jurisdiction, but one answer for why two 2-meter (~6 ft) extension cords in series is inadvisable compared to a single 4 meter cord is that it’s not an apples-to-apples comparison. Longer cords necessarily have to be built differently than shorter cords, not only because of electrical codes (eg the NEC in USA) or product safety specs (eg UL, CSA) but also being well-designed for their expected use. There’s also the human aspect, which all good designs must account for as well.

    Here in the USA, common extension cord lengths are ~2 m (6 ft), ~7.5 m (25 ft), ~15 m (50 ft), and ~30 m (100 ft). Of those cords, the common wire gauge used might be 18 AWG (~1 mm^2), 14 AWG (~2 mm^2), 16 AWG (~1.5 mm^2), and 12 AWG (~3.5 mm^2). I’ve intentionally rounded the metric units so they’re more analogous to common wire gauges outside the USA. Finally, the insulation used can be anything from “thin, indoor only” to “heavy, abrasion and sunlight resistant”. And while the USA technically has a boat-load of AC connectors, the grand majority will use the standard 2-pin or 3-pin 120v connector, formally known as NEMA 1-15 and NEMA 5-15 respectively. What this means is that chaining extension cords is both possible and somewhat common. The problem is one of mismatched designs.

    From a cursory search on the website of a major USA home improvement store, the smallest wire gauge used for a 100 ft cable is 16 AWG. The largest is 10 AWG (nb: smaller numbers mean bigger wire). That thinner cable is marketed for outdoor use. The thicker cable indicates its use “indoor/outdoor” and for heavy-duty applications. It is also branded with a major power-tool company, which would be appropriate as power tools often draw high current.

    Whereas looking at 6 ft extension cords, most are 16 AWG but a few were 18 AWG (thinner than 16) or 14 AWG (thicker). But I could not find any thicker cables than that, certainly nothing that uses 10 AWG (~6 mm^2). The “heavy duty” cables of this length also used only 16 AWG wire.

    Because electrical resistance is additive in series, and because Ohm’s Law governs the voltage lost at the end of a cord, the use of insufficiently large conductors can cause voltage issues for high-current appliances. Appliances for USA-spec generally require 120 Volts +/- 10%, with utilities aiming to provide 120 Volts +/- 5% from the outlets. This means a “sufficient” power cord should not have a voltage drop of more than 6 volts, give or take. Of course, a high-current appliance will also cause a larger voltage drop than a low-current device, so we only consider the former case.

    For a machine that draws 12 Amps attached to a 100 ft extension cord made of 18 AWG wire, the voltage drop would be 15 volts. This is bad for the machine, which now sees a lower voltage than expected. Had the cord been made of 12 AWG wire, the drop is an acceptable 3 volts.

    So if you’re operating construction tools, it would be a terrible idea to use three random 6-ft cables, and you should instead use a single 25-ft cable. Even though it’s longer than you need, the fact is that most 25 ft cables use thicker conductors, which reduces the voltage drop overall.

    But there’s also that peaky human factor. Sure, there would also be more connectors which could come loose, but the really pressing issue with daisy chained cords is when people do that indoors, because they only have light-duty 6 ft cables handy. And for that Christmas tree, they need to use attach three cables together to go beneath the hallway rug.

    This is essentially the worst-case scenario: using thin conductor cords, with thin insulation, underneath very flammable household surfaces, which are also trodden upon by foot traffic. Every step on that cord weakens the insulation and fatigues the conductors. Over time, the conductor becomes thinner where it’s being fatigued, and this increases the voltage drop. An unfortunate result of a voltage drop is that it generates heat. For a cable which is uniformly thin, this heat is spread over the whole length. But for localized conductor damage, the heat is pin-point… directly under a flammable rug.

    In the USA, some 3300 house fires started from an extension cord. Because these cords are not within the walls, they are usually beyond the control of often-strict building/electrical codes, something that’s been critiqued by a prominent YouTuber. The US CPSC even goes so far as to create memes to promote their messaging that space heaters – a common, high-current appliance – should not be used with extension cords or strips.

    CPSC meme about space heaters

    Of course, from an electrical perspective, even a ten-long chain of dinky extension cords would have no problem powering just a single LED night light. But it’s reasonable to ask: 1) is this just asking to be struck down by fate, 2) are there better alternatives like thicker/longer cords, and 3) why isn’t there an outlet where you need it?

    (There’s also a scenario where too long or thin of an extension cord can cause a circuit breaker to fail to trip during a short circuit, but it’s fairly esoteric and this post is quite long now)

    In short, the blanket recommendation to avoid daisy-chaining cords is to avoid the nasty and sometimes fatal results when that can go wrong, even with it might not always play out that way. There’s almost always something safer than can be done than daisy chaining.

  • DragonsInARoom@lemmy.world
    link
    fedilink
    arrow-up
    7
    arrow-down
    1
    ·
    23 hours ago

    Resistance increases over longer distance cable, and increased load from appliances. (Especially don’t with american electrics, they aren’t fused so the wire can overheat and set fire to the surroundings.)

    • kevincox@lemmy.ml
      link
      fedilink
      arrow-up
      6
      ·
      21 hours ago

      To clarify a bit, the benefit of the UK system isn’t the end device having a fuse, but the cable itself having a fuse.

      In the US the setup would be something like

      1. Wall has 20A wiring.
      2. Electrical panel has 20A fuse to avoid the wire in the wall from overheating.
      3. Extension cord is designed for 10A
      4. You plug in 2 10A devices to the extension cord.
      5. The wall wiring is fine, it can take 20A.
      6. The circuit breaker doesn’t trip as it is also 20A.
      7. The extension cord overheats and starts a fire.

      In the UK the 10A extension cord will have its own 10A fuse in the plug. So when you turn on the two 10A devices the fuse in the extension cord will blow and prevent the extension cord from overheating.

      • clockwork_octopus@lemmy.world
        link
        fedilink
        English
        arrow-up
        4
        arrow-down
        1
        ·
        15 hours ago

        Bold of you to assume that the wall outlet would have a 20a breaker. Most don’t, unless they’re in a kitchen.

        But you’re right about the resistance. Also, most extension cords are undersized for the loads they pull, they’re commonly made with 16 or even 18awg wire, further increasing resistance (which translates to heat).

        Source: am electrician in US

        • kevincox@lemmy.ml
          link
          fedilink
          arrow-up
          2
          ·
          10 hours ago

          The circuit power doesn’t matter for the example. I was just picking easy numbers. You can have the same problem as long as the rating of the extension cord is less than the circuit breaker. (And as you pointed that out this is a very common case due to the frequently low rating of extension cords.)

    • Baku@aussie.zoneOP
      link
      fedilink
      English
      arrow-up
      4
      ·
      1 day ago

      I think that would be more relevant to power boards than extension cords. Unless nomenclature is different elsewhere, extension cords here generally only have a single plug. Although there are usually warnings to not run things like clothes dryers or portable stovetops through an extension cord because it can apparently melt the cable. Truthfully, I don’t entirely get that either, as I would’ve assumed they’d be built to the same standard as internal wiring

        • Baku@aussie.zoneOP
          link
          fedilink
          English
          arrow-up
          5
          ·
          1 day ago

          Ah, no worries! I’m not sure if it’s even universally agreed upon across native English speakers. Where I’m from though, a powerboard (or power strip in other parts of the world) has one plug that then leads on to usually 4 or more additional power points/sockets. An extension cord on the other hand usually only allows a single device be connected to it (whether that’s another extension cord or something else)

  • BentiGorlich@gehirneimer.de
    link
    fedilink
    arrow-up
    8
    arrow-down
    3
    ·
    24 hours ago

    I think it is partly a US specific problem as the quality of the extension cords really suck. Meanwhile in Eurpoe (or at least in Germany) the extension cords actually use the same wire grade as your in wall wires, so there is a basically no difference in using daisy chained extension cords versus different wall outlets (as long as the outlets are in the same curcuit)

    • Atherel@lemmy.dbzer0.com
      link
      fedilink
      arrow-up
      2
      ·
      11 hours ago

      Yep, came here to write the same. We have 240V and not 120V like the US. To power the same appliance in the US you have double the Ampere and therefore higher risk of fire (correct me if I’m wrong)

      • BentiGorlich@gehirneimer.de
        link
        fedilink
        arrow-up
        3
        arrow-down
        1
        ·
        11 hours ago

        I strongly disagree… We just have higher standards regarding power wires. Since we have more voltage running through the wires we need tougher ones, but that is what regulation is for

        • Atherel@lemmy.dbzer0.com
          link
          fedilink
          arrow-up
          2
          ·
          3 hours ago

          So the higher Ampere doesn’t require thicker cables? Genuinely asking. The higher standards and regulations are absolutely part of why you don’t hear this rule here.

          • Successful_Try543@feddit.org
            link
            fedilink
            arrow-up
            2
            ·
            edit-2
            24 minutes ago

            Yes, as US uses an voltage of 120 V, the current drawn by a load P is approximately double the current drawn by the same load P in EU with 230 V. Thus, the wires used in Europe only need approximately half the cross section compared to US. However, the insulation of the wires needs to be of higher standard.

          • BentiGorlich@gehirneimer.de
            link
            fedilink
            arrow-up
            1
            arrow-down
            1
            ·
            2 hours ago

            Its higher voltage,but yes It does. However the higher standards take care of that, so you don’t have too weak power cables available

    • tortiscu@discuss.tchncs.de
      link
      fedilink
      arrow-up
      5
      ·
      14 hours ago

      Not necessarily exactly the same wires, but all rated for 16A, so the circuit beaker will trip long before any wire gets a chance to heat up

      • BentiGorlich@gehirneimer.de
        link
        fedilink
        arrow-up
        1
        arrow-down
        3
        ·
        23 hours ago

        I mean it is hard to find out if they are the exact same, since power strips often don’t specify it, but from handling both I’d say they are pretty much the same…

  • Rhynoplaz@lemmy.world
    link
    fedilink
    arrow-up
    5
    ·
    1 day ago

    I would also like to hear an expert opinion on this. Never really made sense to me either, but it also doesn’t sound unreasonable.